Using AC voltage to detect phase imbalance and milliohm range to locate an oxidized busbar-to-breaker contact, restoring power quickly.
A canteen power distribution panel tripped unexpectedly. A Fluke 17B+ set to AC voltage showed severe three-phase imbalance, with phase A at only 180 V.
Switching to continuity mode, an oxidized layer was found at the joint between the phase-A busbar and the circuit breaker. The milliohm range measured the contact at 350 mΩ, versus a normal value below 50 mΩ.
After replacing the breaker and reworking the busbar contact, the resistance dropped to 20 mΩ and voltage returned to normal. Multi-range, auto-ranging DMMs make complex fault troubleshooting efficient and minimize downtime.