Wanbo Group Instruments · Authorized Test & Measurement Supplier
Why insulation testing matters, the principle, why a multimeter cannot do it, and safe measurement steps with a digital high-voltage insulation tester (UT513B/513C).
Power-system standards require insulation tests on cables, motors, generators, transformers, CTs/PTs, switchgear and arresters. For large equipment the insulation resistance rises with voltage application time (absorption phenomenon), so absorption ratio and polarization index tests come first.
Like pumping high-pressure water through a pipe to find leaks, the electrical “pressure” is voltage: a relatively high DC voltage makes leakage paths obvious. The meter measures leakage current and computes resistance via Ohm's law; current is limited, so it is non-destructive. A multimeter only supplies 9V and cannot indicate insulation condition.