Product overview: Fluke MDA-550 Series III Motor Drive Analyzer Fluke Premium Care eligible .fpc-contain { width: 100%; display: grid; grid-template-columns: 40% 40%; gap: 5%; padding: 30px; background-color: #0072CE; color: white !important; border-radius: 5px; } .fpc-means-grid { display: grid; grid-template-columns: 10% 85%; gap: 5%; margin-bottom: 30px; margin-top: 20px; } .white-button { background-color: white !important; border: none !important; border-radius: 10px !important; } .fpc-right-column { background-color: #3B82F6 !important; border-radius: 5px; padding: 15px; } .whats-included-grid { display: grid; grid-template-columns: 10% 90%; } Fluke Premium Care Plan Reduce unplanned expenses and get the most out of your tools with a Fluke Premium Care Plan. Investing in Fluke Premium Care plans means: Smoother Operations Enhanced Productivity Maintaining High Standards Learn More What's included: Repair Manufacturing Defects Accidental Damage and Repair Replacement of Damaged Accessories Annual Calibration or Performance Check Expedited Calibration and Repair Expedited Shipping Software Updates Priority Tech Support Loaner Equipment Learn more Simplify complex motor-drive troubleshooting with guided test setups and automated drive measurements that provide reliable, repeatable test results. The Fluke MDA 550 Motor-Drive Analyzer saves time and eliminates the hassle of setting up complex measurements, while simplifying motor-drive troubleshooting. Simply select a test and the step-by-step guided measurements show you where to make voltage and current connections, while the preset measurement profiles ensure you will capture all the data you need for each critical motor-drive section—from the input to the output, the DC bus, and the motor itself. From basic to advanced measurements, the MDA-550 has you covered, and with a built-in report generator you can quickly and easily generate as-found, and as-left reports with confidence. The MDA-550 is the ideal portable motor-drive analysis test tool and can help safely locate and troubleshoot typical problems on inverter type motor-drive systems. Measure key motor-drive parameters including voltage, current, DC Bus voltage level and AC ripple, voltage and current unbalance and harmonics, voltage modulation, and motor shaft voltage discharges. Perform extended harmonics measurements to identify the effects of low and high order harmonics on your electrical power system. Conduct guided measurements for motor-drive input, DC bus, drive output, motor input and shaft measurements with graphical step-by-step voltage and current connection diagrams. Use simplified measurement setup with preset measurement profiles to automatically trigger data collection based on the chosen test procedure. Create reports quickly and easily that are perfect for documenting troubleshooting and collaborative work with others. Measure additional electrical parameters with full 500 MHz oscilloscope, meter and recording capability for complete range of electrical and electronic measurement on industrial systems. The Fluke MDA-550 Motor Drive Analyzer uses guided test measurements to make analysis easier than ever Drive input Measure input voltage and current to quickly see whether values are within acceptable limits by comparing the drive’s nominal rated voltage to the actual supplied voltage. Then, check the input current to determine if the current is within the maximum rating and the conductors are suitably sized. You can also check whether the harmonic distortion is within an acceptable level by visually inspecting the waveform shape or by viewing the harmonics spec¬trum screen which shows both the total harmonic distortion and individual harmonics. Voltage and current unbalance Check the voltage unbalance at the input terminals so you can ensure the phase unbalance is not too high (> 6-8 %), and that the phase rotation is correct. You can also check the current unbalance, as excessive unbalance may indicate a drive rectifier problem. Extended harmonic measurements Excessive harmonics are not just a threat to your rotating machines but also to other equipment connected to the electrical power system. The MDA-550 provides the ability to discover the harmon¬ics of the motor-drive but can also discover the possible effects of inverter switching electronics. The MDA-550 has three harmonic ranges, 1st to 51st Harmonics, 1 to 9 kHz and 9 kHz to 150 kHz giving the ability to detect any harmonic pollution problems. DC bus In a motor-drive the conversion of AC to DC inside the drive is criti¬cal, having the correct voltage and adequate smoothing with low ripple is required for the best drive performance. High ripple volt¬age may be an indicator of failed capacitors or incorrect sizing of the connected motor. The record function can be used to check DC bus performance dynamically in the operating mode while a load is applied. Drive output Check the output of the drive focusing both on voltage t
• AfricaEnglish
• AfricaFrançais
• Middle EastEnglish
• Americas
• ArgentinaEspañol
• ColombiaEspañol
• BoliviaEspañol
• BrazilPortuguês
• CanadaEnglish
• CanadaFrançais
• ChileEspañol
• Costa RicaEspañol